Sıkça Sorulan Teknik Sorular

Soru Sorun

What is the contact resistance per pole for C60 range of MCBs.

The contact resistance per pole for C60 range of MCBs is as tabulated below:

C60 Test for In at 50 Hz, Value per pole

Rated Current (A) Impedance (milliohm)
0.5 8800
0.75 5267
1 2300
1.2 1667
1.5 933
2 638
3 248
4 150
5 100
6 75
7 57.14
8 43.25
10 17
13 11
15 10
16 10.13
20 7.35
25 4.88
30 3.47
32 3.47
35 2.57
40 2.88
50 1.9
60 1.5
63 1.52

 Note: The resistance is equivalent to the impedance as the inductance between the contacts is negligible.